Multi-voltage revers. Act.

Multi-voltage reversible electric actuator

LED status indicator

Constantly lit LEDdel constamment allumée
If the actuator is operating correctly with no fouls, the LED shows a constantly lit light.
LED flashes with 2 blinksDEL 2 clignotements
If the actuator has been left in "manual" mode, the actuator's motor runs but doesn't drive the output shaft. After a preset time, the actuator knows that because the torque limiter has not been activated and that the motor is running, it must be in manual.
LED flashes ON/OFFDEl 1 seul clignotement
When the actuator senses an inpending valve jam, the electronic torque limiter is activated, and upon activation, repeatly flashes the LED on and off.
ON/OFF or failsafe actuators

Function : ON/OFF version

- Power open, power close
- Stays in position upon power failure

Function : failsafe version

- Power open, power close. Trickle charges battery in either open or closed position.
- Actuator driven by battery power to preset failsafe position upon power failure.
- Actuator returns to pre-failure position on power resumption
- Failsafe can be either NC (normally closed) or NO (normally open)

Modulating actuators

Function : modulating version

- Power open, power close. Actuator movement controlled.
- Standard operation : 4mA or 0V = actuator closed, 20 mA or 10V = actuator open (can ben reversed)
- Standard operation : actuator closes on loss of control signal, stays put if loss of main power.
- Output signal provided as standard (in same format as supply signal).

* except for actuator AE140 and AE300

12 to 24 VAC/VDC and 85 to 240 VAC/VDC

Wiring diagram (ON/OFF or failsafe actuators)

cablage actionneur tout ou rien
inverseur de polarité = Change-over switch : to supply continuous signal until end of travel is reached
inverseur de polarité = Reversing polarity switch : to supply continuous signal until end of travel is reached

Isolated dry contacts : factory set at 0° and 90° - switch rated 220V 5A
Anti-condensation heater : operates only while power is on. Power can be left on permanently

Wiring diagram (modulating actuators)

Power supply 4-20mA or 0-10VDC - control signal - input and output End of travel confirmation
cablage actionneur de régulation
Isolated dry contacts : factory set at 0° and 90° - switched rated 220V 5A